NETWORK SYSTEMS


Description

The Series 7450 Network System is designed to provide the user with a simple to use yet technically sophisticated way to gather information and provide control for a wide variety of industrial equipment.  This is done using a modular approach that insures that there is just the right hardware mix for the specific application. The user interfaces to the system via a single Ethernet or RS232 connection.

Generally, the system consists of two types of modules.  The Master I/O module is the heart of the data collection and control as well as allowing for an optional Internal PC.  The Slave I/O is the expansion element that allows additional I/O based on application requirements. 

The minimum hardware configuration consists of the Master I/0 module alone.  The high end software runs on a host system and communicates over the Ethernet or RS232 connection. 

The second level brings some of the computing power on board with the addition of a Internal PC, power supply and hard drive.  There is room available to mount this hardware in the Master Module Enclosure.

The third level provides additional I/O to the system.  In this case the Slave I/O module would be added.  It provides I/O expansion for the application.  It integrates seamlessly into the network, since the Master I/O handles all of the power and communications with the Slave.  The network still uses the same single Ethernet or RS232 connection. The master and slave communicate via a separate serial bus (RS485).

Each module is housed in matching 19” rack mount black aluminum enclosure.  They are different heights, but the width and depth are the same.  Since they are standard “u” rack heights they will mount in any combination in standard racks.  Additionally, the handles and rack ears may be removed and they can be stacked.  Interlocking strips are available to fix them into one large stack.  Also, feet are available that will allow them to sit on the bench.

The Master I/O module use a universal power inputs that will work from 100 to 240 VAC.  

 

Back to Top

Features and Specifications

I/O MASTER SPECIFICATIONS
EXPANDABLE

A SLAVE MODULE CAN BE ADDED, INCREASING THE NUMBER OF INPUTS AND OUTPUTS

4 ANALOG INPUT

EACH INPUT CAN BE CONFIGURED FOR 0 TO 5V, 0 TO 10V 

0 – 20mA OR 4 –20mA OPERATION

EACH INPUT CAN BE CONFIGURED FOR SINGLE OR DIFFERENTIAL OPERATION

ALL INPUT LINES ARE “EMI” PROTECTED

ALL INPUTS ARE REVERSE POLARITY PROTECTED

8 DIGITAL INPUTS

2 OF THE 8 INPUTS CAN BE CONFIGURED FOR  COUNTER APPLICATIONS

CONFIGURABLE TO OPERATE AT 5, 12 OR 24 VDC

CONFIGURABLE FOR NPN OR PNP OPERATION

ALL INPUT LINES ARE “EMI” PROTECTED

ALL INPUTS ARE REVERSE POLARITY PROTECTED

2 THERMOCOUPLE INPUTS

CONFIGURABLE FOR TYPE J OR TYPE K THERMOCOUPLES

2 RTD INPUTS

CONFIGURABLE FOR 100 OHM OR 1000 OHM SENSORS

CONFIGURABLE FOR SI OR JIS TYPE, PLATINUM

2 ANALOG OUTPUTS

SINGLE ENDED, CONFIGURABLE FOR 0 TO 5V, 0 T0 10V, 0 – 20mA OR 4 – 20mA OPERATION.

OUTPUTS REVERSED POLARITY PROTECTED

“EMI” PROTECTED

6 DIGITAL OUTPUTS

4 RELAY OUTPUTS, DRY CONTACT 

– RATED 2 AMPS, 30VDC/240VAC

2 OUTPUTS, OPEN COLLECTOR TRANSISTOR

OUTPUTS REVERSED POLARITY PROTECTED

“EMI” PROTECTED

LED INDICATORS

POWER, STATUS, CPU

ETHERNET INTERFACE

IEEE 802.3

10/100 BASE T

RJ45 CONNECTOR

RS232 COMMUNICATIONS PORT

DB9 CONNECTOR

“EMI” PROTECTED

9600 TO 115K BAUD RATE, AUTO NEGOTIATED

ISOLATION

ALL INPUTS AND OUTPUTS ELECTRICALLY ISOLATED FROM MICROPROCESSOR

MASTER / SLAVE INTERCONNECT

RS485

ENCLOSURE

19 INCH RACK MOUNT 

OVERLAY

LEXAN

OUTPUT POWER

24 VDC, 2 AMPS

12 VDC, 2 AMPS

5  VDC, 2 AMPS

 INPUT POWER

110/220VAC, 50/60Hz

MOUNTING PROVISIONS

PROVISIONS FOR THE MOUNTING OF AN INTERNAL PC, POWER SUPPLY AND HARD DRIVE

 
I/O SLAVE SPECIFICATIONS
4 ANALOG INPUTS

EACH INPUT CAN BE CONFIGURED FOR 0 TO 5V, 0 TO 10V

0 – 20mA OR 4 –20mA OPERATION

EACH INPUT CAN BE CONFIGURED FOR SINGLE OR DIFFERENTIAL OPERATION

ALL INPUT LINES ARE “EMI” PROTECTED

ALL INPUTS ARE REVERSE POLARITY PROTECTED

8 DIGITAL INPUTS

2 OF THE 8 INPUTS CAN BE CONFIGURED FOR  COUNTER APPLICATIONS

CONFIGURABLE TO OPERATE AT 5, 12 OR 24 VDC

CONFIGURABLE FOR NPN OR PNP OPERATION

ALL INPUT LINES ARE “EMI” PROTECTED

ALL INPUTS ARE REVERSE POLARITY PROTECTED

2 THERMOCOUPLE INPUTS

CONFIGURABLE FOR TYPE J OR TYPE K THERMOCOUPLES

2 RTD INPUTS

CONFIGURABLE FOR 100 OHM OR 1000 OHM SENSORS

CONFIGURABLE FOR SI OR JIS TYPE, PLATINUM

2 ANALOG OUTPUTS

SINGLE ENDED, CONFIGURABLE FOR 0 TO 5V, 0 T0 10V, 0 – 20mA OR 4 – 20mA OPERATION.

OUTPUTS REVERSED POLARITY PROTECTED

“EMI” PROTECTED

6 DIGITAL OUTPUTS

4 RELAY OUTPUTS, DRY CONTACT 

– RATED 2 AMPS, 30VDC/240VAC

2 OUTPUTS, OPEN COLLECTOR TRANSISTOR

OUTPUTS REVERSED POLARITY PROTECTED

“EMI” PROTECTED

LED INDICATORS

POWER, STATUS, CPU

MASTER / SLAVE INTERCONNECT

RS485

ENCLOSURE

19 INCH RACK MOUNT 

OVERLAY

LEXAN

Back to Top

Available Models

MODEL

MODULE TYPE

7450M

MASTER

7450S SLAVE
Back to Top

Manuals and Drawings

Manual_Procon_7450_60_745000-00_REV1.pdf

Back to Top

Related Products

 

Back to Top
 

JPC CONTROLS

3081 Elm Point Industrial Dr., St. Charles, MO  63301

Phone:  636-946-3300    Fax:  636-724-2492    Email:  sales@jpccontrols.com

www.jpccontrols.com

Copyright © 2010 JPC Controls Incorporated